| DC Voltage
|
12, 24, 48, 60, 96, 120, 144, 168, 192,216, 240, 264, 288, 312 and 336V DC
|
Input
|
Electronic overload detector
Electronic short circuit detector
Low battery voltage detector
|
| Input window
|
-17% +20%
|
|
|
| Efficiency at full load
|
>90% depending on the model
|
|
|
|
|
|
| AC Voltage
|
230V AC
|
Dielectric strength
|
3000V AC, for 1 minute
|
| Regulation
|
±2%
|
Isolation
|
>10 MW
|
| Power rating
|
see table above (kVA=kW rating)
|
Ventilation
|
>Forced air
|
| Total harmonic distortion
|
<3%
|
Audible noise
|
at 1m <45 dB
|
| Type of output
|
wave Pure sine-wave
|
Protection grade as per
UNE 20 324 78 IR regulations
|
IP20
|
| Technology
|
PWM
|
Operating temperature
|
0°C to 40°C
|
| Frequency
|
50Hz ±0.05%
|
Operating elevation
|
Sea level to 2,400m
|
| Overload
|
Up to 150% for 4.5 sec
|
Relative humidity
|
0-95% (non condensing)
|
| Power factor
|
0.7 lead to 0.7 lagging
|
|
|
| Crest factor
|
3 to 1
|
|
|
|
|
|
| Input
|
Electronic overload detector
Electronic short circuit detector
Low battery voltage detector
|
|
|
|