Products
PW1 Single Phase UPS 600V

Technology
 CONTACT US NOW!
 Do you need some help in
 selecting a UPS?
 To download a PDF version of this Data
 sheet click the link below.  


 If you do not have Acrobat reader  you can  download  it for free  here!

 Automatic shutdown Software and UPS
 Monitoring


 SEC software, which operates using the RS232  interface, is offered with this range of UPS to enable  total monitoring and control.
 
Allows controlled, unattended shutdown of one or more operating systems.
 
Compatible with all major operating systems (Windows ’95,Windows NT, OS/2, Novell Netware, SCO UNIX , Solaris, HP, UX, IBM-AIX).
 
Allows all UPS operating parameters to be viewed and monitored.
 
Allows actions to be configured, eg. Sending network messages, e-mail or pager.
 
Provides full function reporting.
 
Dial UPS remote monitoring allows the UPS to be monitored by our central monitoring station.
 
 Custom Solutions

 The PowerWorks single phase UPS range offers a
 wide choice of power ratings and autonomies. In
 addition, we are able to supply equipment to meet
 companies specific requirements, with different input
 and output frequencies or voltages. Units come in
 floor standing or rack -mountable housing (up to
 4kV).
 Contact us to discuss your specific requirements.
 Do you need some help in
 selecting a UPS?
On-line double conversion with static by-pass

Application
Provides true on-line protection for critical work stations, servers and networking equipment as well as telecom, security and processing applications.

Benefits & Features

  Power factor correction on input. 

  Galvanic isolation transformer eliminates electrical noise.

  Full micro processor control. 

  Perfect regulated sine-wave output voltage. 

  Automatic static by-pass is provided as standard. 

  Large input voltage window, without discharging the batteries.

  All units are configured to suit individual markets. 

  High frequency IGBT, PWM Inverter for high efficiency and silent
  operation. 

  Full RS232 interface, compatible with System Enhancement (SE)
  protocol, running PowerMon, SmartMon and NetMon for full
  network control capability. 

  SNMP Ready.
  MODEL   Power Rating Autonomy at typical load (min)*   UPS Dimensions (mm)   UPS Weight
kg
  kVA   kW 10   Width   Height   Depth
 PW1-UPS-600 0.6 0.42 10 245 500 650 13
 PW1-UPS-700 0.7 0.49 10 145 220 400 13
 PW1-UPS-800 0.8 0.56 10 245 500 600 15
 PW1-UPS-1000 1 0.7 10 145 220 400 15.5
 PW1-UPS-1200 1.2 0.7 10 245 500 650 70
 PW1-UPS-1500 1.5 0.84 10 145 220 400 18
 PW1-UPS-1600 1.6 1.05 10 245 500 650 79
 PW1-UPS-2000 2 1.12 10 195 380 470 30
 PW1-UPS-2200 2.2 1.4 10 245 500 650 87
 PW1-UPS-3000 3 1.54 10 195 380 470 35
 PW1-UPS-3000 3 2.1 10 245 500 650 99
 PW1-UPS-40000 4 2.8 10 245 500 650 120
 PW1-UPS-5000 5 4 10 245 500 650 131
 PW1-UPS-7500 7.5 6 10 350 690 780 197
 PW1-UPS-10000 10 8 10 420 920 920 222
 PW1-UPS-12500 12.5 10 10 600 1235 750 297
 PW1-UPS-15000 15 12 10 600 1235 750 420
 PW1-UPS-20000 20 16 10 600 1235 750 450




General Technical Characteristics
 
Technology      Batteries
Type


Control
On-line, double conversion with galvanic isolation and static by-pass.

Microprocessor
Type

Recharge Time
Sealed lead-acid maintenance free

Typically 2 hours from depleted batteries to 80% capacity
Input Communications
Voltage

Frequency
Single Phase 184V to 264V

50 or 60HzHz ± 5%
Relay Interface


RS-232/485 port
Serial port for automatic closure of files and subsequent shutdown of the UPS.

Incorporated as standard feature on 5kVA and above.
Output Environment
Voltage

Regulation


Frequency


Wave Form

Efficiency


Total harmonic distortion  

Overload Capability



Crest Factor
230V/240V*

±1% during steady state ±2% during transient state.

50 or60Hz synchronized with mains. During mains failure ± 0.05%

Pure sine-wave

>90%

2% at full load

Up to 150% for 20s before transfer to by-pass


3 to 1
Power Factor

Input/Output efficiency

Audible noise

Operating temperature

EMC


Safety

Packaging

Output connection




Relative humidity

Operating altitude
0.99 at the input

>90%

<45dB at 1m

0to 40°C

EN50091-2,EN55011, level B, IEC1000-4-1,2,3,4,5

EN50091-1

Without CFC, recyclable

Output receptacles (up to 4kVA) Terminal block (from 5kVA and above)

0 to 95% non condensing

Sea level to 2,400m

By-pass
Type


Operating Criteria

Overload capability

Transfer for inverter to mains

Transfer from mains to inverter
Automatic in case of overload or inverter failure

Controlled by microprocessor

Up to 200%. Short circuit for 40ms

Immediate for overloads above 150%


Automatic, following synchronization with mains.